• RDR300 Series

RDR300 Series

Measuring Distance
50 meters
Measurement Technology
Non-contact FMCW Measurement
Cable Connection
3-Wire and 2-Wire Connection

ORION FMCW Radar Level Sensor is used for non-contact, continuous level and volume measurement of liquid and solid materials in open and closed tanks. With its sealed keypad, it displays the measured value as level, distance (cm, m) or volume (liter, m3).

TEKLİF İSTE

Application Areas


Orion FMCW (RDR300 series) radar level sensor is used for continuous level and volume measurement of liquid and solid materials in non-contact open and closed tanks. A 4-button sealed keypad and LCD display are used to set the parameters of the level to be measured and the distance range. Fault indicator informs you about the operation and fault status of the FMCW radar. In addition, it can display the measured value as level, distance (cm, m) or volume (liter, m3). The device uses FMCW (pulse) technology instead of measurement time. It generates and sends a signal scan with frequency increasing over time. The transmitted signal is reflected by the measured surface. The reflected signal is picked up by the antenna. The frequency difference between the transmitted and received signals is directly proportional to the distance between the measured surface and the sensor.

Official Compliance


EN61000-6-4: 2001 Generic emission standard. Industrial envoirements.

EN61000-6-2: 2005 Generic immunity standard. Industrial envoirements.

EN61010-1: 2001 Safety requirements for electrical equipment for measurement, control and laboratory use

Usage Areas: Sand, Cement, Waste Water, Clean Water, Milk and Dairy Products, Soft Drink, Oil, Gasoline, Diesel, Pharmaceutical Industry, Dolomite, Calcite, Perlite Gypsum, Lime, Fine Sand, Stone, Ceramic, Pulverized Coal Powder, Flour and Feed, Plastic Granules.

Measuring Distance 50 meters
Measurement Technology Non-contact FMCW Measurement
Cable Connection 3-Wire and 2-Wire Connection
Output Signal Standard 4-20mA and MODBUS RS485
Switch 2 Relay Contacts
Protection Class IP68
Operating Temperature -20°C+80°C
Signal Propagation Angle Less Than 12 °
Precision 0.2% at Set Measurement Range
Connection DN100 Flange or Hanger Fork
Body Aluminum